Error code Description Classification Remedy Blocking time [s]
2250 CiA: Continuous overcurrent (inside the device) Error

• Check motor and wiring for short circuits.
• Check brake resistor and wiring.
• Check motor circuit (delta connection, star connection).
• Check setting of the motor data.

5
2320 Short circuit or earth leakage on the motor side Error

• Check motor cable.
• Check the length of the motor cable.
• Use shorter or lower-capacitance motor cable.

5
2340 CiA: Short circuit (inside the device) Error

• Check motor cable for short circuit. 

5
2350 CiA: i²*t overload (thermal state) Error

• Check drive sizing.
• Check machine/driven mechanics for excessive load.
• Check setting of the motor data.
• Reduce values for slip compensation (P315.01, P315.02) and oscillation damping (P318.01, P318.02).

5
2382 Error: Device utilization (Ixt) too high Error

• Check drive sizing.
• Reduce maximum overload current of the inverter (P324.00).
• In case of high mass inertias, reduce maximum overload current of the inverter (P324.00) to 150 %.

3
2383 Warning: Device utilization (Ixt) too high Warning

• Check drive sizing

0
3120 Mains phase fault Error

• Check mains connection wiring.
• Check fuses.

0
3210 DC bus overvoltage Error

• Reduce dynamic performance of the load profile.
• Check mains voltage.
• Check settings for the brake energy management.
• Connect brake resistor to the power unit and activate the integrated brake chopper.
(P706.01 = 0: brake resistance).

0
3211 Warning: DC bus overvoltage Warning

• Reduce dynamic performance of the load profile.
• Check mains voltage.
• Check settings for the brake energy management.
• Connect brake resistor to the power unit and activate the integrated brake chopper.
(P706.01 = 0: brake resistance).

0
3220 DC bus undervoltage Trouble

• Check mains voltage.
• Check fuses.
• Check DC-bus voltage (P105.00).
• Check mains settings.

0
3221 Warning: DC bus undervoltage Warning

• Check mains voltage.
• Check fuses.
• Check DC-bus voltage (P105.00).
• Check mains settings.

0
3222 DC-bus voltage too low for switch-on Warning

• Check mains voltage.
• Check fuses.
• Check mains settings.

0
4210 PU: Overtemperature fault Error

• Check mains voltage.
• Provide for a sufficient cooling of the device (display of the heatsink temperature in P117.01).
• Clean fan and ventilation slots. If required, replace fan.
• Reduce switching frequency (P305.00).

0
4281 Heatsink fan warning Warning

• Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can
then be removed.

0
4310 Error: Motor overtemperature Error

• Check drive sizing.
• Check motor temperature sensor and wiring (terminals X109/T1 and X109/T2).

5
5112 24 V supply critical Warning

• Check optional external 24 V voltage supply (terminal X3/24E), if connected.
• Check mains voltage. 

0
5180 24 V supply overload Warning

• Check 24 V output and digital outputs for earth fault or overload.

0
6280 Trigger/functions connected incorrectly Trouble

• Check and correct the assignment of the triggers to the functions.
• With keypad or network control, the two functions “Inverter enable” (P400.01) and “Run” (P400.02) can also
be set to “Constant TRUE [1]” to start the motor.

0
7180 Motor overcurrent Error

• Check motor load.
• Check drive sizing.
• Adapt the set error threshold (P353.01).

1
9080 Keypad removed Error

• Connect the keypad again or activate another control source.

0
FF02 Error: Brake resistor overload Error

• Check drive sizing.
• Check settings for the brake energy management.
• Note! The error will be reset if the thermal load falls below the error threshold (P707.09) - 20 %.

5
FF06 Motor overspeed Error

• Adapt the maximum motor speed (P322.00) and the error threshold (P350.01).

1
FF36 Warning: Brake resistor overload Warning

• Check drive sizing.
• Check settings for the brake energy management.
• Note! The warning will be reset if the thermal load falls below the warning threshold (P707.08) - 20 %.

0
FF37 Automatic start disabled Error

• Deactivate start command and reset error.

0
FF85 Keypad full control active Warning

• Press the CTRL key to exit control mode.

0